CONDPAC installations

General

CONDPAC systems are fully automatically controlled, with reactor-based reactive current compensations equipped with high-quality, self-healing
dry capacitors.
The modular, space-saving design facilitates simple, rapid expansion and adaptation to the optimum compensation output.

Design and equipment

Switch cabinet: Sheet steel cabinet, colour RAL 7035, base 100 mm black, 50 mm panel, door hinge on the right side, lock DB 5 mm, protection class outside IP 40, roof IP 20C
Max. equipment fitting: 300 kVar or 6 modules per cabinet unit Modules
Modules: Condpac modules for 600 mm or 800 mm cabinet widths fitted with dry AM condensers, filter circuit chokes, switching contactors, busbar system and stage guard with NH-LTS 00
Reactive power controller: microprocessor-controlled, including under-voltage tripping, temperature monitoring, fan control and fault indication
Control switches: mounted in the door
Ventilation: from 50 kVar with fans in the roof sheet
Connection: from below or above on the connection kit
Line fuse: onsite
Current transformer: onsite, transformer ratio … / 5

 

Technical specifications

Mains voltage: 400 V, 50 Hz
Condenser rated voltage: 525 V, 50 Hz
Control voltage: 400 V , 50 Hz
Stage power: 3.1, 6.25, 12.5, 25, 50 kVar
Choke frequency: 189 Hz, p = 7 %
130 Hz, p = 14.8 %
Power loss: max. 8 W/kvar
Temperature limit: -5° to +45° C