NICER installations
General
NICER systems are fully automatically controlled, reactor-based reactive current compensations equipped with impregnated, harmonic-resistant capacitors of the H series.Nicer systems are used in grids with heavy harmonic distortion as well as generally where the service life is meant to be a few decades.
Design and equipment
Switch cabinet: | Sheet steel cabinet, colour RAL 7035, base 100 mm black, 50 mm panel, door hinge on the right side, lock DB 5 mm, protection class outside IP 40, roof IP 20C |
Max. equipment fitting: | 200 kVar or 4 condensers per cabinet unit |
Modules: | NICER module fitted with filter circuit chokes, switching contactors, busbar system and stage guard with NH-LTS 00 |
Reactive power controller: | microprocessor-controlled, including under-voltage tripping, temperature monitoring, fan control and fault indication |
Control switches: | mounted in the door |
Ventilation: | from 50 kVar with fans in the roof sheet |
Connection: | from below or above on the connection kit |
Line fuse: | onsite |
Current transformer: | onsite, transformer ratio … / 5 |
Design: | halogen-free |
Technical specifications
Mains voltage: | 400 V, 50 Hz |
Condenser rated voltage: | 525 V, 50 Hz |
Control voltage: | 400 V , 50 Hz |
Stage power: | 25, 50 kVar |
Choke frequency: | 189 Hz, p = 7 % 130 Hz, p = 14.8 % |
Power loss: | ca. 8 W/kvar |
Temperature limit: | -5° to +45° C |