CONDPAC installations
General
CONDPAC systems are fully automatically controlled, with reactor-based reactive current compensations equipped with high-quality, self-healingdry capacitors.
The modular, space-saving design facilitates simple, rapid expansion and adaptation to the optimum compensation output.
Design and equipment
Switch cabinet: | Sheet steel cabinet, colour RAL 7035, base 100 mm black, 50 mm panel, door hinge on the right side, lock DB 5 mm, protection class outside IP 40, roof IP 20C |
Max. equipment fitting: | 300 kVar or 6 modules per cabinet unit Modules |
Modules: | Condpac modules for 600 mm or 800 mm cabinet widths fitted with dry AM condensers, filter circuit chokes, switching contactors, busbar system and stage guard with NH-LTS 00 |
Reactive power controller: | microprocessor-controlled, including under-voltage tripping, temperature monitoring, fan control and fault indication |
Control switches: | mounted in the door |
Ventilation: | from 50 kVar with fans in the roof sheet |
Connection: | from below or above on the connection kit |
Line fuse: | onsite |
Current transformer: | onsite, transformer ratio … / 5 |
Technical specifications
Mains voltage: | 400 V, 50 Hz |
Condenser rated voltage: | 525 V, 50 Hz |
Control voltage: | 400 V , 50 Hz |
Stage power: | 3.1, 6.25, 12.5, 25, 50 kVar |
Choke frequency: | 189 Hz, p = 7 % 130 Hz, p = 14.8 % |
Power loss: | max. 8 W/kvar |
Temperature limit: | -5° to +45° C |