TRIPAC installations

General

TRIPAC systems are thyristor-controlled, fully automatically controlled, with reactor-based reactive current compensations equipped with high-quality, self-healing dry capacitors.
The use of thyristors instead of switch contactors is recommended for very dynamic grid conditions with fast load changes or in grids with unstable voltage conditions.

Special features

  • Reactive power is compensated in real time
  • Zero current switching of the capacitors increases their service life
  • No mechanical wear of switchgear
  • Thyristors are maintenance-free

Design and equipment

Switch cabinet: Sheet steel cabinet, colour RAL 7035, base 100 mm black, 50 mm panel, door hinge on the right side, lock DB 5 mm, protection class outside IP 40, roof IP 20C
Max. equipment fitting: 300 kVar or 6 modules per cabinet unit
Modules: TRIPAC modules fitted with AM dry condensers, filter circuit chokes, thyristor unit, busbar system and stage guard with NH-LTS 00
Reactive power controller: BLR-CM controller, microprocessor-controlled, including under-voltage tripping, temperature monitoring, fan control and fault indication
Control switches: mounted in the door
Ventilation: with fans in the roof sheet
Connection: from below or above on the connection kit
Line fuse: onsite
Current transformer: onsite, transformer ratio … / 5

 

Technical specifications

Mains voltage: 400 V, 50 Hz
Condenser rated voltage: 525 V, 50 Hz
Control voltage: 400 V , 50 Hz
Stage power: 12.5, 25, 50 kVar
Choke frequency: 189 Hz, p = 7 %
130 Hz, p = 14.8 %
Thyristor switching times: Typically 20 ms
maximum of 40 ms
Switching at zero current flow
Power loss: ca. 12 W/kVar
Temperature limit: -5° to +45° C